TECHNICAL DATASHEET CliQ II DIN Rail Power Supply 24 V 91.2 W 1 Phase, NEC Class 2 / DRP-24V100W1NN Highlights & Features Universal AC input voltage range Power will not de-rate for the entire input voltage range UL 1310 safety approval NEC Class 2 and Limited Power Source (LPS) approvals Built-in active PFC, PF > 0.99 115 Vac Full corrosion resistant aluminium casing Conforms to harmonic current IEC/EN 61000-3-2, Class A Conformal coating on PCBAs to protect against common dust and chemical pollutants Overvoltage / Overcurrent / Over Temperature / Short Circuit Protections Certified according to IEC/EN/UL 62368-1 Safety Standards CB Certified for worldwide use Model Number: DRP-24V100W1NN Unit Weight: 0.60 kg (1.32 lb) Dimensions (L x W x D): 124 x 40 x 124 mm (4.88 x 1.57 x 4.88 inch) General Description Deltas CliQ II DIN Rail Power Supply series with UL 1310 and NEC Class 2 approvals offers start-of-the-art designs made to withstand harsh industrial environments. The rugged Aluminium case is both shock and vibration resistant according to IEC 60068-2 and adheres to IP20 protection level. The DRP-24V100W1NN can be used in general industrial applications, especially for dry indoor condition with the advantage of lower wiring costs for a system due to its compliance with NEC Class 2 requirements. The NEC (National Electrical Code) is a North American standard, which is regarded as a law in most North American states. The NEC describes the installation of electric conductors and equipments within or on buildings. Like the rest of the models in the CliQ series, conformal coating is applied on the PCBAs to protect against dust and chemical pollutants. The Class 2 power units operates over a wide temperature range of -25C to +80 and universal AC input voltage range from 85 Vac to 264 Vac, the power will not de-rate for the entire input voltage range value. The product also includes overvoltage, overload, over temperature and short circuit protections for the output. Model Information CliQ II DIN Rail Power Supply Model Number Input Voltage Range Rated Output Voltage Rated Output Current DRP-24V100W1NN 85-264 Vac (120375 Vdc) 24 Vdc 3.80 A Model Numbering DR P 24V 100W 1 N N DIN Rail Power Supply Output Voltage Output Power Single Phase NEC Class 2 N - Metal Case, without Class I, Div 2 All parameters are specified at 25C ambient and AC input unless otherwise indicated. 1 www.DeltaPSU.com (June 2021, Rev. 05) TECHNICAL DATASHEET CliQ II DIN Rail Power Supply 24 V 91.2 W 1 Phase, NEC Class 2 / DRP-24V100W1NN Specifications Input Ratings / Characteristics Nominal Input Voltage 100-240 Vac Input Voltage Range 85-264 Vac Nominal Input Frequency 50-60 Hz Input Frequency Range 47-63 Hz DC Input Voltage Range* 120-375 Vdc Input Current < 1.00 A 115 Vac, < 0.53A 230 Vac Efficiency at 100% Load > 88.0% 115 Vac, > 89.0% 230 Vac Max Power Dissipation 0% load < 0.7 W 115 Vac, < 0.8 W 230 Vac 100% load < 12.4 W 115 Vac, < 11.2 W 230 Vac Max Inrush Current (Cold Start) < 30 A 115 Vac, < 60 A 230 Vac Power Factor > 0.99 115 Vac, > 0.94 230 Vac Leakage Current < 0.5 mA 240 Vac *Fulfills tested condition, additional testing for system approval might be necessary. Output Ratings / Characteristics** Nominal Output Voltage 24 Vdc Factory Set Point Tolerance 24 Vdc 2% Output Voltage Adjustment Range 22-24 Vdc Output Current 0-3.80 A (91.2 W max) Output Power 91.2 W Line Regulation < 0.5% ( 85-264 Vac input, 100% load) Load Regulation < 1.0% at -25C to +25C < 2.0% at +25C to +50C ( 85-264 Vac input, 0-100% load) PARD*** (20 MHz) < 150 mVpp Rise Time < 100 ms nominal input (100% load) Start-up Time < 2,000 ms nominal input (100% load) Hold-up Time > 20 ms 115 Vac, > 30 ms 230 Vac (100% load) Dynamic Response 5% 85-264 Vac input, 0-100% load (Overshoot & Undershoot O/P Voltage) (Slew Rate: 0.1 A/s, 50% duty cycle 5 Hz to 1 kHz) Start-up with Capacitive Loads 8,000 F Max **For power de-rating from 50C to 80C, see power de-rating on page 3. ***PARD is measured with an AC coupling mode, 5 cm wires, and in parallel with 0.1 F ceramic capacitor & 47 F electrolytic capacitor. All parameters are specified at 25C ambient and AC input unless otherwise indicated. 2 www.DeltaPSU.com (June 2021, Rev. 05)